Tel: +86-769-88996313

E-mail: sf@camda.cc

413 KVA Standby Diesel Generator

413 KVA Standby Diesel Generator

Diesel generator set from 18 to 1320 kW; Cummins engine; Leroy somer or Stamford alternator; Factory price and factory outlet; CE/ISO and BV/TUV/SGS verified; OEM and ODM manufacturer; ...

Send InquiryChat Now
Product Details









KDGC330S



kdgc360

Ratings

Standby Power

kVA

413

kW

330

Prime  Power

kVA

375

kW

300

Voltage type

50Hz,380/220V, 3 phases and 4 wires

 Performance Data

Engine Brand & Model

Cummins NTAA855-G7

Alternator Brand & Model

LSA47.2VS2

Control System

Deepsea DSE6120

Standard Noise Level@7m (Soundproof Sets)

75 dBA

Circuit Breaker Type

3 Poles MCCB

Frequency & Phase

50Hz, 3Phases + 4Wires

Engine Speed (RPM)

1500

Fuel Consumption (L/hr)

100% Load

85.4

75% Load

64.1

50% Load

46.9

25% Load

23.5

Dimensions and Weights

Content

Open type

Soundproof Sets

Dimensions: (mm)

L

3200

4200

W

1150

1400

H

1900

2150

Weights (kg)

3570

4990


When the color of exhaust gas is abnormal:

No.

Malfaunction and causes

Remedy

1

Black exhaust gas:
(1)Engine’s over-load
(2)Wrong valve clearance, not good valve seat, so that lead to valve leaking

(1)Reduce load and make it in the regulars scope

(2)Adjust valve clearance and check seal conical surface to delete the shortage

2

White exhaust gas

When engine start, there is incomplete burning in cylinders.

Increase the speed and load within suitable volume and run for longer time.

3

Blue exhaust gas:
The single cylinder power is not enuogh and decreased one by one. Besides, there is gas leaking and black smoke for gas inlet pipe, and with abnormal knocking, etc.

(1) Air filter is blocked

(2) Piston ring is jammed or over-wearing; the chamfer angle of piston ring is installed in wrong angle and make oil enter into burning house.

(3) Long time low-load operation; Big clearance between piston and cylinder liner, so that make oil enter into burning house.

(4) There is too much oil in oil pan.

(1)Dismantle and clean air filter
(2)Dismantle piston ring and change it if it is necessary
(3)Increase the engine load in a suitable volume
(4)Add oil to oil pan according to the oil ruler.

4

There is moisture condensation in exhaust gas; There is crack in cylinder cover and then make coolant enter into cylinder.

Change the cylinder cover