120 KW Gas Generator

Ratings *Ratings at 0.8 power factor Performance Data * The above fuel consumption is calculate with the natural gas whose heat value is 35.8MJ/Nm 3 Dimensions and Weights Engine Brand & Model: HGT6C Engine Data Inspection in operating: ◇When the generator set is on the normal working hours,...

Send Inquiry
Product Details
KDGH120-G    50HZ1(001).jpg



Ratings

Rated  Power

kVA

150

kW

120

Voltage type

50Hz, 380/220V, 3 phases and 4 wires

*Ratings at 0.8 power factor

 

Performance Data

Engine Brand & Model

HGN14

Alternator Brand & Model

LSA44.3L10/120KW

Control System

Deepsea DSE6120

Standard Noise Level@7m (Soundproof Sets)

75 dBA

Circuit Breaker Type

3 Poles MCCB

Frequency & Phase

50hz 3Phases + 4Wires

Engine Speed (RPM)

1500

Fuel Consumption (Nm3/hr) 100% Load

37.71

* The above fuel consumption is calculate with the natural gas whose heat value is 35.8MJ/Nm3

 

Dimensions and Weights

Content

Open type

Soundproof Sets

Dimensions: (mm)

L

2800

3500

W

850

1300

H

1480

1900

Weights (kg)

1850

2850

 

Engine Brand & Model: HGN14

Engine Data

No. of Cylinders

6

Engine power(KW)

145

Cycle

4 Stroke

Cylinder Type

Wet

Bore * Stroke (mm)

140 * 152

Compression Ratio

11:1

Induction

Aftercooled

Displacement (L)

14

Cooling Method

Water cooled

Governing Type

Electronic

Starting method

24V DC motor

Coolant capacity, including radiator (L)

66.8

Lubricant Oil

15W40-CF4 or above grade

Oil pan capacity (L)

36


◇Open the gas fuel switch, adjust the gas pressure to 0.8-1.6Kpa. 

◇Open the power supply switch and ensure indicator light is on, then start genset according to the control system operating specifications.

◇Turn off gas fuel switch if genset fail to start for three times. In order to discharge the residual gas, please start genset again. But before that, please check the malfunction and troubleshooting.

◇After genset starting, the speed should be controlled about 1500RPM and note the reading of oil pressure carefully. If the oil pressure have no indicator, stop genset and check it immediately. 

◇If the genset operate normally, turn off air switch and increase the load gradually.

 

Please Note: air switch have the protective equipment of decompression. So it can be turn off when the genset voltage reach 70% rated voltage. (When turn off switch, the shift handle should be button up firstly and then turn off upwards). After the switch turn on, if genset voltage is reduced to 40-70% rated voltage, this switch will jump upwards once again, but it will not be the "off" position, all these situation is normal.