200 KW Gas Generator

Ratings *Ratings at 0.8 power factor Performance Data * The above fuel consumption is calculate with the natural gas whose heat value is 35.8MJ/Nm 3 Dimensions and Weights Engine Brand & Model: HGKT19 Engine Data Steps for genset stop: ◇Unload the load gradually and disconnect the air switch...

Send Inquiry
Product Details
KDGH200-G    50HZ200


Ratings

Rated  Power

kVA

250

kW

200

Voltage type

50Hz, 380/220V, 3 phases and 4 wires

*Ratings at 0.8 power factor

 

Performance Data

Engine Brand & Model

HGNT14

Alternator Brand & Model

LSA46.3S5/200KW

Control System

Deepsea DSE6120

Standard Noise Level@7m (Soundproof Sets)

75 dBA

Circuit Breaker Type

3 Poles MCCB

Frequency & Phase

50hz 3Phases + 4Wires

Engine Speed (RPM)

1500

Fuel Consumption (Nm3/hr) 100% Load

64.05

* The above fuel consumption is calculate with the natural gas whose heat value is 35.8MJ/Nm3

 

Dimensions and Weights

Content

Open type

Soundproof Sets

Dimensions: (mm)

L

3150

4200

W

1100

1500

H

1800

2250

Weights (kg)

2525

5025

 

Engine Brand & Model: HGNT14

Engine Data

No. of Cylinders

6  in-line

Engine power(KW)

240

Cycle

4 Stroke

Cylinder Type

Wet

Bore * Stroke (mm)

140 * 152

Compression Ratio

11:01

Induction

Turbocharged and Aftercooled

Displacement (L)

14

Cooling Method

Water cooled

Governing Type

Electronic

Starting method

24V DC motor

Coolant capacity, including radiator (L)

66.8

Lubricant Oil

15W40-CF4 or above grade

Oil pan capacity (L)

36


 

 

Steps for genset stop:

Unload the load gradually and disconnect the air switch automatically. 

In the conditions of no-load, reduce the speed to 600-700rmp gradually. Stop the generator set when gas engine water temperature drop to or below 70.

When the ambient temperature is below 5, release all the water of gas generator set cooling system such as water cooler, circulating water pumps, oil coolers, generator body, etc to prevent freezing. There is no need to release water if add antifreezi to generator set.

Clean the whole generating unit, and prepare for the next use. 

In order to fit for the natural gas or biogas, there are two main renovations: One is for the mixture of natural gas /biogas with air according to the reasonable proportion, the second is ignite the mixing gas quickly to improve the power efficiency. So except the same and similar component with corresponding disel generator, users can know that the special part of the gas generator set: Gas supply system, ignition system and sensor, electronic governor.

 

 

Requirements on the floor:

The floor must be flat. Its concrete structure must be thicker than 250mm for the genset500kW. If genset power above 500kW, its thickness will be 300 to 500mm. 

Caution: Floor must be solid and basement or hollow is forbidden.

Users can decide the weight and dimension of the foundation for genset.

The thickness of foundation and load capability of floor can be work out as follows:

Load capability of floor is depend on the weight of the whole genset (includin fuel and water), genset dimension and shock-proof pad quantity, if genset base frame is fixed on floor directly, then the load of floor will be:

Load of floor =weight of genset / area of slide rail

If equipped with shock-proof pad, and genset stands on each pad:

Load of floor =weight of genset / (area of shock-proof pad ×quantity)

Therefore, load of floor can be decreased by increasing the quantity of shock-proof pad.

The large pressure of floor=weight of shock-proof pad loading the most weight / area of shock-proof pad.


2.jpg