250 KW Gas Generator

Ratings *Ratings at 0.8 power factor Performance Data * The above fuel consumption is calculate with the natural gas whose heat value is 35.8MJ/Nm 3 Dimensions and Weights Engine Brand & Model: HGKT19 Engine Data Idling speed running after starting: After everything prepared, open the gas...

Send Inquiry
Product Details
KDGH300-NG     50HZ1(001).jpg


Ratings

Rated  Power

kVA

375

kW

300

Voltage type

50Hz, 380/220V, 3 phases and 4 wires

*Ratings at 0.8 power factor


Performance Data

Engine Brand & Model

HGKT19

Alternator Brand & Model

LSA47.2VS2/300KW

Control System

Deepsea DSE6120

Standard Noise Level@7m (Soundproof Sets)

75 dBA

Circuit Breaker Type

3 Poles MCCB

Frequency & Phase

50hz 3Phases + 4Wires

Engine Speed (RPM)

1500

Fuel Consumption (Nm3/hr) 100% Load

86.19

* The above fuel consumption is calculate with the natural gas whose heat value is 35.8MJ/Nm3


Dimensions and Weights

Content

Open type

Soundproof Sets

Dimensions: (mm)

L

3500

5600

W

1250

2000

H

2020

2500

Weights (kg)

3380

4985


Engine Brand & Model: HGKT19

Engine Data

No. of Cylinders

6  in-line

Engine power(KW)

341

Cycle

4 Stroke

Cylinder Type

Wet

Bore * Stroke (mm)

159 * 159

Compression Ratio

11.5:1

Induction

Turbocharged & Aftercooled

Displacement (L)

18.9

Cooling Method

Water cooled

Governing Type

Electronic

Starting method

24V DC motor

Coolant capacity, including radiator (L)

115

Lubricant Oil

15W40-CF4 or above grade

Oil pan capacity (L)

87


Idling speed running after starting: 

After everything prepared, open the gas valva and power connection, turn the key, and then press the button. After starting, note the oil pressure guage to make sure that the oil pressure is normal. It needs to keep the generator idle running for a while to observe if all the parts of generator operate normally. Once problems occurred, solve the problem immediately. Also idle running can increase the temperature increasing will be useful for the generator set running.


Recycling:

Good ventilation system need adequate air inflows and outflows, and circulate freely in the room, so the plant room must have enough space to make free air circulation, so that the temperature of the plant room can be balanced, and with no arrogance stranded.


Notes:

1. Hot exhaust from genset should be lead out by air-leading mantle. Air-leading and outlet hole in the wall shall be well sealed in order to prevent steam backflow to decrease the cooling effect.

2. Cooling air must be leaded to outdoor, its temperature should be as lower as possible. Outlet exit and air-leading mantle should be designed according to the structure of power room.

3. The temperature in power room must less than 43℃, otherwise it will low the power, and will cause electrical component damage. If the temperature higher than 43℃, we should enhance indoor ventilation.It would be better to use two air-turbine, which installed in air-leading pipes. One is for turbining cooling air indoor while another is leading hot air outdoor.

4. Outlet area requirements: outlet area must be approx.1.3 times of radiator. If the outlet equipped with protection net, we should increase the size of the outlet according to the area of net. If the outlet equipped ventilation board, we should increase the size of the outlet in accordance with the effective area.

5. Inlet area requirements: Inlet area must be approx.1.3 times of radiator. If the inlet equipped with protection net, we should increase the size of the inlet according to the area of net. If the inlet equipped the ventilation board, we should increase the size of the inlet in accordance with the effective area.


2.jpg


Hot Tags: 250 KW gas Generator, China, suppliers, manufacturers, factory